Yueqing Vorax Electric CO.,LTD

Type and hit enter

All Products

Home /RCCB TYPE B /High Immunity Residual Current Circuit Breaker Type B

High Immunity Residual Current Circuit Breaker Type B
Place of OriginCHINA
Brand NameHAROK
Model NumberVKL11


Products Details
Degree Of ProtectionIP20Rated Frequency50/60Hz
Product NameRCCB TYPE BRated Voltage Un2P 230/240V~; 4P 400/415V~
Rated Residual Operating Current I△n30mA, 100mA, 300mA, 500mA(Instantaneous & K-short Time Delayed (G, ASi)); 100mA, 300mA, 500mA (100mA, 300mA, 500mA)Rated Current In16A, 25A, 32A, 40A, 63A, 80A, 100A
Rated Insulation Voltage Ui500VRated Impulse Withstand Voltage Uimp4 KV (1.2/50μs)
High Light

32A Residual Current Circuit Breaker, 63A 30mA RCCB type B, High immunity rccb 63a 100ma


Leave A Message
Products Description

High immunity Residual Current Circuit Breaker Type B

 

1. General

 

1.1 Function

VKL11B RCCB and VKL11B+ RCCB is appearance design, compact structure, good reliability, and high safety. They are universal residual current circuit breaker.

Residual current circuit breaker type B are suitable for domestic as well as industrial applications, where are used frequency inverters, PV plant, EV chargers and similar elements. B type provides a sensitivity to residual AC, pulsating and smooth DC current, together with high frequencies up to 1 kHz.

Residual current circuit breaker type B+ meet full type B feature , with additional tripping values are defined up to 20KHZ and they are below 420mA.

They are based on electronic technology, which brings advantages of more accurate measuring of residual current and, as a consequence, reduction of unwanted tripping. These devices also do not suffer with magnetization of the tripping unit.

 

1.2 Selection

 

Detectable wave form

 

Type BHigh Immunity Residual Current Circuit Breaker Type B 0

Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.

 

Type B+High Immunity Residual Current Circuit Breaker Type B 1High Immunity Residual Current Circuit Breaker Type B 2

Meet full type B feature , with additional tripping values are defined up to 20KHZ and they are below 420mA

 

Tripping sensitivity

30mA - additional protection against direct contact.

100mA - co-ordinated with the earth system according to the formula IΔn<50/R, to provide protection against indirect contacts;

300mA - protection against indirect contacts, as well as fire hazard.

 

Tripping time

Instantaneous It ensures instantaneous tripping(without time-delay).

Short time delay

Selective (time delay)

 

1.3 Approvals and certificates

High Immunity Residual Current Circuit Breaker Type B 3

 

 

RCCB | Residual Current Circuit Breaker

 

2. Technical parameters

 

TypeBB+
Electrical
Design according toIEC/EN 62423, IEC/EN 61008-1, OVE E8601

VDE 0664-400
Current test marks as printed onto the device
Rated voltage Un

2P: 230/240V AC

4P: 400/415V AC

Rated frequency fn50/60Hz
Mode of operation

"A type functionality: voltage independent

B and B+ type functionality: voltage dependent"

Operation voltage electronic50 – 264V AC
Voltage range test circuit

2P: 184 – 264V AC

4P: 184 – 440V AC

Rated current In16A, 25A, 32A, 40A, 63A, 80A, 100A

Rated residual

operating

current I△n

Instantaneous30mA, 100mA, 300mA, 500mA30mA, 100mA, 300mA
K-short time delayed (G, ASi)30mA, 100mA, 300mA, 500mA30mA, 100mA, 300mA
S- selective100mA, 300mA, 500mA100mA, 300mA
SensitivityAlternating, pulsed and smooth direct currents
High frequency up to 1 kHZHigh frequency up to 20kHZ
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp4 kV (1.2/50μs)
Rated conditional short-circuit current Inc10 kA
Rated making and breaking capacity Im1500 A
Peak withstand current

3 kA (8/20 μs) surge current proof

5 kA (8/20 μs) surge current proof for type S

Electrical isolation> 4 mm contact space

Maximum back-up fuse

In = 16-100A

Short circuit and overload protection

100 A gG/gL

Endurance

(operating cycles)

electrical components≥ 2000
mechanical components≥ 4000
Mechanical
Degree of protectionIP20
Upper and lower terminalsopen mounted / lift terminals
Terminal capacity1 - 25 mm2
Terminal torque2 - 2.5 Nm
Busbar thickness0.8 - 2 mm
Operating temperature-25°C ... +55°C
Storage- and transport temperature-40°C ... +70°C
Resistance to climatic conditionsIEC/EN 61008
Contact position indicatormechanical red / green
Supply possibilitytop or bottom
Mounting positionany

 

 

3. Special features regarding the use of SIQUENCE universal current-sensitive residual current circuit breaker (Type B and Type B+)

 

3.1 Applications

Typical applications that are vulnerable to smooth DC residual currents:

- Frequency converters with a three-phase connection

- Medical equipment such as X-ray equipment or CT machines

- Photovoltaic or UPS systems

- Connection points (wall boxes, charging stations) for electric vehicles

- Elevator controllers

- Pipeline trace heating

- Test setups in laboratories

- Construction sites in accordance with BGI 608 information leaflet (Electronic equipment on construction sites)

- Charging stations for battery-powered forklift trucks

- Cranes of all kinds

- Mixing plants if relevant loads are connected

- Variable-speed machine tools, such as milling and grinding machines or lathes

 

4. Wiring diagrams

 

High Immunity Residual Current Circuit Breaker Type B 4High Immunity Residual Current Circuit Breaker Type B 5

 

5. Tripping characteristics

 

B type

High Immunity Residual Current Circuit Breaker Type B 6

 

 

 

 

 

 

 

 

 

 

 

 

 

6. Dimensions (mm)

 

High Immunity Residual Current Circuit Breaker Type B 7High Immunity Residual Current Circuit Breaker Type B 8

Product Description:

RCCB TYPE B is a high-performance residual current circuit breaker, designed with rated making and breaking capacity Im of 1500A, electrical endurance of ≥ 2000, degree of protection of IP20, rated residual operating current I△n of 30mA, 100mA, 300mA, 500mA (Instantaneous & K-short Time Delayed (G, ASi)); 100mA, 300mA, 500mA (100mA, 300mA, 500mA) and rated frequency of 50/60Hz. It provides excellent protection against electric shock and fire caused by earth leakage current and features high immunity. It is ideal for use in residential, commercial and industrial applications.

 

Features:

  • Product Name: High immunity RCCB TYPE B

  • Sensitivity: Alternating, Pulsed and Smooth Direct Currents (High Frequency up to 1 KHZ)

  • Mechanical Endurance: ≥ 4000

  • Rated insulation voltage Ui: 500V

  • Electrical Endurance: ≥ 2000

  • Busbar thickness: 0.8 - 2 Mm

 

Applications:

Harok VKL11 Super Immunised RCCB TYPE B

Harok's VKL11 Super Immunised RCCB TYPE B is a highly-reliable voltage dependent circuit breaker designed for use in various indoor applications. With a rated insulation voltage of 500V, it provides superior protection with a degree of protection IP20 and electrical endurance of ≥ 2000. The circuit breaker is manufactured with a rated frequency of 50/60Hz. It is also designed with a voltage dependent mode of operation, making it a safe and durable choice for a variety of applications.

Harok's VKL11 Super Immunised RCCB TYPE B is suitable for use in various indoor environments ranging from residential and commercial premises to industrial facilities. It is compliant with the IEC 61009-1 standard for residual current circuit breakers and is ideal for use in applications where safety and reliability are of paramount importance. Furthermore, it is an excellent choice for areas where frequent switching is required, as it ensures accurate and reliable protection from overcurrent and short circuit.

Harok's VKL11 Super Immunised RCCB TYPE B is a cost-effective solution for a variety of applications. With its superior protection, electrical endurance and reliable operation, it is an excellent choice for a wide range of indoor applications.

 

Technical Parameters:

Product NameRCCB TYPE B
Rated Frequency50/60Hz
Rated impulse withstand voltage Uimp4 KV (1.2/50μs)
Mechanical Endurance≥ 4000
Rated making and breaking capacity Im1500A
Degree of protectionIP20
Rated voltage Un2P 230/240V~; 4P 400/415V~
Rated current In16A, 25A, 32A, 40A, 63A, 80A, 100A
SensitivityAlternating, Pulsed And Smooth Direct Currents (High Frequency Up To 1 KHZ)
StandardIEC/EN 62423, IEC/EN 61008-1, OVE E8601
Special FeatureSuper immunised RCCB, High immunity RCCB

 

Customization:

HAROK VKL11 High Immunity RCCB TYPE B

Brand Name: HAROK

Model Number: VKL11

Place of Origin: CHINA

Electrical Endurance: ≥ 2000

Rated current In: 16A, 25A, 32A, 40A, 63A, 80A, 100A

Degree of protection: IP20

Rated voltage Un: 2P 230/240V~; 4P 400/415V~

Rated residual operating current I△n: 30mA, 100mA, 300mA, 500mA (Instantaneous & K-short Time Delayed (G, ASi)); 100mA, 300mA, 500mA (100mA, 300mA, 500mA)

Super immunised RCCB, High immunity RCCB.

 

Packing and Shipping:

Packaging and Shipping for RCCB TYPE B:

  • The product is packed in a cardboard box with a protective foam layer;

  • The box is sealed with plastic tape;

  • The box is labeled with product and company information;

  • The product is shipped via air freight or ground freight, depending on customer preference.


Recommended Products
  • VKL11 RCCB Type B+

    View Details
  • Super Immunised Residual Current Circuit Breaker Type B

    View Details
  • VKL11 RCCB TYPE B VDE KEMA NF 80A Residual Current Operated Circuit Breaker With 4 KV Rated Impulse Withstand Voltage

    View Details
  • High Immunity RCCB TYPE B- Rated Voltage Un 2P 230/240V~ And 4P 400/415V~ With Superior Mechanical Endurance Of ≥ 4000

    View Details