Type and hit enter
Degree Of Protection | IP20 | Rated Frequency | 50/60Hz |
---|---|---|---|
Product Name | RCCB TYPE B | Rated Voltage Un | 2P 230/240V~; 4P 400/415V~ |
Rated Residual Operating Current I△n | 30mA, 100mA, 300mA, 500mA(Instantaneous & K-short Time Delayed (G, ASi)); 100mA, 300mA, 500mA (100mA, 300mA, 500mA) | Rated Current In | 16A, 25A, 32A, 40A, 63A, 80A, 100A |
Rated Insulation Voltage Ui | 500V | Rated Impulse Withstand Voltage Uimp | 4 KV (1.2/50μs) |
High Light | 32A Residual Current Circuit Breaker, 63A 30mA RCCB type B, High immunity rccb 63a 100ma |
High immunity Residual Current Circuit Breaker Type B
1. General
1.1 Function
VKL11B RCCB and VKL11B+ RCCB is appearance design, compact structure, good reliability, and high safety. They are universal residual current circuit breaker.
Residual current circuit breaker type B are suitable for domestic as well as industrial applications, where are used frequency inverters, PV plant, EV chargers and similar elements. B type provides a sensitivity to residual AC, pulsating and smooth DC current, together with high frequencies up to 1 kHz.
Residual current circuit breaker type B+ meet full type B feature , with additional tripping values are defined up to 20KHZ and they are below 420mA.
They are based on electronic technology, which brings advantages of more accurate measuring of residual current and, as a consequence, reduction of unwanted tripping. These devices also do not suffer with magnetization of the tripping unit.
1.2 Selection
Detectable wave form
Type B
Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.
Type B+
Meet full type B feature , with additional tripping values are defined up to 20KHZ and they are below 420mA
Tripping sensitivity
30mA - additional protection against direct contact.
100mA - co-ordinated with the earth system according to the formula IΔn<50/R, to provide protection against indirect contacts;
300mA - protection against indirect contacts, as well as fire hazard.
Tripping time
Instantaneous It ensures instantaneous tripping(without time-delay).
Short time delay
Selective (time delay)
1.3 Approvals and certificates
RCCB | Residual Current Circuit Breaker
2. Technical parameters
Type | B | B+ | ||
Electrical | ||||
Design according to | IEC/EN 62423, IEC/EN 61008-1, OVE E8601 | |||
VDE 0664-400 | ||||
Current test marks as printed onto the device | ||||
Rated voltage Un | 2P: 230/240V AC 4P: 400/415V AC | |||
Rated frequency fn | 50/60Hz | |||
Mode of operation | "A type functionality: voltage independent B and B+ type functionality: voltage dependent" | |||
Operation voltage electronic | 50 – 264V AC | |||
Voltage range test circuit | 2P: 184 – 264V AC 4P: 184 – 440V AC | |||
Rated current In | 16A, 25A, 32A, 40A, 63A, 80A, 100A | |||
Rated residual operating current I△n | Instantaneous | 30mA, 100mA, 300mA, 500mA | 30mA, 100mA, 300mA | |
K-short time delayed (G, ASi) | 30mA, 100mA, 300mA, 500mA | 30mA, 100mA, 300mA | ||
S- selective | 100mA, 300mA, 500mA | 100mA, 300mA | ||
Sensitivity | Alternating, pulsed and smooth direct currents | |||
High frequency up to 1 kHZ | High frequency up to 20kHZ | |||
Rated insulation voltage Ui | 500 V | |||
Rated impulse withstand voltage Uimp | 4 kV (1.2/50μs) | |||
Rated conditional short-circuit current Inc | 10 kA | |||
Rated making and breaking capacity Im | 1500 A | |||
Peak withstand current | 3 kA (8/20 μs) surge current proof 5 kA (8/20 μs) surge current proof for type S | |||
Electrical isolation | > 4 mm contact space | |||
Maximum back-up fuse In = 16-100A | Short circuit and overload protection 100 A gG/gL | |||
Endurance (operating cycles) | electrical components | ≥ 2000 | ||
mechanical components | ≥ 4000 | |||
Mechanical | ||||
Degree of protection | IP20 | |||
Upper and lower terminals | open mounted / lift terminals | |||
Terminal capacity | 1 - 25 mm2 | |||
Terminal torque | 2 - 2.5 Nm | |||
Busbar thickness | 0.8 - 2 mm | |||
Operating temperature | -25°C ... +55°C | |||
Storage- and transport temperature | -40°C ... +70°C | |||
Resistance to climatic conditions | IEC/EN 61008 | |||
Contact position indicator | mechanical red / green | |||
Supply possibility | top or bottom | |||
Mounting position | any |
3. Special features regarding the use of SIQUENCE universal current-sensitive residual current circuit breaker (Type B and Type B+)
3.1 Applications
Typical applications that are vulnerable to smooth DC residual currents:
- Frequency converters with a three-phase connection
- Medical equipment such as X-ray equipment or CT machines
- Photovoltaic or UPS systems
- Connection points (wall boxes, charging stations) for electric vehicles
- Elevator controllers
- Pipeline trace heating
- Test setups in laboratories
- Construction sites in accordance with BGI 608 information leaflet (Electronic equipment on construction sites)
- Charging stations for battery-powered forklift trucks
- Cranes of all kinds
- Mixing plants if relevant loads are connected
- Variable-speed machine tools, such as milling and grinding machines or lathes
4. Wiring diagrams
5. Tripping characteristics
B type
6. Dimensions (mm)
RCCB TYPE B is a high-performance residual current circuit breaker, designed with rated making and breaking capacity Im of 1500A, electrical endurance of ≥ 2000, degree of protection of IP20, rated residual operating current I△n of 30mA, 100mA, 300mA, 500mA (Instantaneous & K-short Time Delayed (G, ASi)); 100mA, 300mA, 500mA (100mA, 300mA, 500mA) and rated frequency of 50/60Hz. It provides excellent protection against electric shock and fire caused by earth leakage current and features high immunity. It is ideal for use in residential, commercial and industrial applications.
Product Name: High immunity RCCB TYPE B
Sensitivity: Alternating, Pulsed and Smooth Direct Currents (High Frequency up to 1 KHZ)
Mechanical Endurance: ≥ 4000
Rated insulation voltage Ui: 500V
Electrical Endurance: ≥ 2000
Busbar thickness: 0.8 - 2 Mm
Harok's VKL11 Super Immunised RCCB TYPE B is a highly-reliable voltage dependent circuit breaker designed for use in various indoor applications. With a rated insulation voltage of 500V, it provides superior protection with a degree of protection IP20 and electrical endurance of ≥ 2000. The circuit breaker is manufactured with a rated frequency of 50/60Hz. It is also designed with a voltage dependent mode of operation, making it a safe and durable choice for a variety of applications.
Harok's VKL11 Super Immunised RCCB TYPE B is suitable for use in various indoor environments ranging from residential and commercial premises to industrial facilities. It is compliant with the IEC 61009-1 standard for residual current circuit breakers and is ideal for use in applications where safety and reliability are of paramount importance. Furthermore, it is an excellent choice for areas where frequent switching is required, as it ensures accurate and reliable protection from overcurrent and short circuit.
Harok's VKL11 Super Immunised RCCB TYPE B is a cost-effective solution for a variety of applications. With its superior protection, electrical endurance and reliable operation, it is an excellent choice for a wide range of indoor applications.
Product Name | RCCB TYPE B |
---|---|
Rated Frequency | 50/60Hz |
Rated impulse withstand voltage Uimp | 4 KV (1.2/50μs) |
Mechanical Endurance | ≥ 4000 |
Rated making and breaking capacity Im | 1500A |
Degree of protection | IP20 |
Rated voltage Un | 2P 230/240V~; 4P 400/415V~ |
Rated current In | 16A, 25A, 32A, 40A, 63A, 80A, 100A |
Sensitivity | Alternating, Pulsed And Smooth Direct Currents (High Frequency Up To 1 KHZ) |
Standard | IEC/EN 62423, IEC/EN 61008-1, OVE E8601 |
Special Feature | Super immunised RCCB, High immunity RCCB |
Brand Name: HAROK
Model Number: VKL11
Place of Origin: CHINA
Electrical Endurance: ≥ 2000
Rated current In: 16A, 25A, 32A, 40A, 63A, 80A, 100A
Degree of protection: IP20
Rated voltage Un: 2P 230/240V~; 4P 400/415V~
Rated residual operating current I△n: 30mA, 100mA, 300mA, 500mA (Instantaneous & K-short Time Delayed (G, ASi)); 100mA, 300mA, 500mA (100mA, 300mA, 500mA)
Super immunised RCCB, High immunity RCCB.
Packaging and Shipping for RCCB TYPE B:
The product is packed in a cardboard box with a protective foam layer;
The box is sealed with plastic tape;
The box is labeled with product and company information;
The product is shipped via air freight or ground freight, depending on customer preference.